PowerFlex 700L Technical Data
Publication 20L-TD001A 19
Frame 3B Power Terminal Locations
Frame 3A/3B Power Terminal Specifications
Item Name Description
Frame
Size
Wire Size Range
(1)
(1)
Maximum/minimum sizes that the terminals will accept - these are not recommendations.
Recommended Tightening
Torque (+
10%)Maximum Minimum
Input Power Wire Lugs
R/L1, S/L2, T/L3
Input power connections on drive 3A 400 MCM 3/0 42 Nm (375 lbin)
3B 1000 MCM 500 MCM 62 Nm (550 lbin)
PE Wire Lug Terminating point for ground wires 3A or 3B 600 MCM # 2 AWG 34 Nm (300 lbin)
Output Power Bus Bar
(2)
U/T1, V/T2, W/T3
(2)
These connections are bus bar type terminations and require the use of lug connectors.
Motor connections 3A or 3B 62 Nm (550 lbin)
DC Bus Test Point Socket
(3)
(2 Terminals; DC+, DC-)
(3)
Use only to verify that DC bus capacitors are discharged before servicing the Power Module. No other external use is permitted.
4 mm socket for DC bus voltage
measurement only
3A or 3B
DC Power Bus Bar
(2)
(4)
(2 Terminals; DC+, DC-)
(4)
Size DC power conductors for current carrying capacity as follows: 400/480V, 1000 Amps; 600/690V, 800 Amps.
DC power from Converter Power Module
to Inverter Power Module
3B 62 Nm (550 lbin)
PORT
MOD
NET A
NET B
24 VDC
TB5
DC POSITIVE
DC NEGATIVE
1 120 VAC
2 PRECHARGE COIL
6 INDUCTOR OVERTEMP
WIRE RANGE:
24-10 AWG
(0.2-4 MM)
4 PR HARGE FEEDBACK
ATE ENABLE
STRIP LENGTH:
0.31 IN (8 MM)
TORQUE:
8 IN-LB
(0.9 N-M)
POWER
STS
Coolant Outlet
Coolant Inlet
➊➎
(Drive shown with
doors removed)