PowerFlex 700L Technical Data
Publication 20L-TD001A 19
Frame 3B Power Terminal Locations
Frame 3A/3B Power Terminal Specifications
Item Name Description
Frame
Size
Wire Size Range
(1)
(1)
Maximum/minimum sizes that the terminals will accept - these are not recommendations.
Recommended Tightening
Torque (+
10%)Maximum Minimum
➊
Input Power Wire Lugs
R/L1, S/L2, T/L3
Input power connections on drive 3A 400 MCM 3/0 42 N•m (375 lb•in)
3B 1000 MCM 500 MCM 62 N•m (550 lb•in)
➋
PE Wire Lug Terminating point for ground wires 3A or 3B 600 MCM # 2 AWG 34 N•m (300 lb•in)
➌
Output Power Bus Bar
(2)
U/T1, V/T2, W/T3
(2)
These connections are bus bar type terminations and require the use of lug connectors.
Motor connections 3A or 3B 62 N•m (550 lb•in)
➍
DC Bus Test Point Socket
(3)
(2 Terminals; DC+, DC-)
(3)
Use only to verify that DC bus capacitors are discharged before servicing the Power Module. No other external use is permitted.
4 mm socket for DC bus voltage
measurement only
3A or 3B — — —
➎
DC Power Bus Bar
(2)
(4)
(2 Terminals; DC+, DC-)
(4)
Size DC power conductors for current carrying capacity as follows: 400/480V, 1000 Amps; 600/690V, 800 Amps.
DC power from Converter Power Module
to Inverter Power Module
3B 62 N•m (550 lb•in)
PORT
MOD
NET A
NET B
24 VDC
TB5
DC POSITIVE
DC NEGATIVE
1 120 VAC
2 PRECHARGE COIL
6 INDUCTOR OVERTEMP
WIRE RANGE:
24-10 AWG
(0.2-4 MM)
4 PR HARGE FEEDBACK
ATE ENABLE
STRIP LENGTH:
0.31 IN (8 MM)
TORQUE:
8 IN-LB
(0.9 N-M)
POWER
STS
Coolant Outlet
Coolant Inlet
➊➎
➋
➌
➍
(Drive shown with
doors removed)